  page 1 of 5 universal power supplies txh 600 series, 600 watt features universal input: 90C264 vac or 120C370 vdc active power factor correction (>0.95) high effciency up to 93% load share function for up to 3 units in parallel adjustable output voltage emi/emc compliance with en 61000-6-3 and en 61000-6-1 remote control input rear side iec-c13 line socket, including mains switch and fuse dc-ok signal and 5 vdc auxiliary output protection against over-voltage, over- temperature, overload and short circuit 3-year product warranty order code output power max. output voltage nom. output current max. effciency typ. txh 120/240/360/480 120 C 480 watt other power models see separate datasheets: www.tracopower.com txh 600-112 540 watt 12 vdc 45 a 90 % txh 600-124 600 watt 24 vdc 25 a 92 % txh 600-148 600 watt 48 vdc 12.5 a 92 % txh 600-154 600 watt 54 vdc 11.1 a 93 % models the txh 600 series models are very compact 600 watt universal power supplies. rear side iec-c13 line socket including mains switch and fuse and the output screw terminal make the connection of these power supplies very easy. sense line, auxil - iary output, remote control, adjustable output voltage, and load share line for up to 3 units in parallel make the units all-purpose applicable. they come with an active power factor correction. the emc characteristic is dedi - cated for applications in industry, it and domestics. the protection against over- voltage, over-temperature, overload and short circuit and a high effciency of up to 93% guaranties a reliable operation. c b scheme ul 60950-1 www.tracopower.com
page 2 of 5 universal power supplies txh 600 series 600 watt input specifications input voltage C nominal 100 C 240 vac C ac range (universal input) 90 C 264 vac C dc range 120 C 370 vdc C output power derating at operation below 110 vac 1%/v (110 - vin) input frequency 47 C 63 hz earth leakage current (240 vac / 63 hz) 3.5 ma max. harmonic limits en 61000-3-2, class a & d C power factor >0.99 at 115 vac, >0.95 at 230 vac input current at full load C at 115 vac / 230 vac rated 8.0 a / 3.5 a typical: 6.0 a / 2.9 a circuit breaker (slow blow fuse) 16 a internal output specifications voltage set accuracy 2 % max. output voltage adjustment range 5 % with internal potentiometer regulation C input variation 1 % max. C load variation (5C100%) 1 % max. minimum load 1% ripple and noise (20 mhz bandwidth) <1% vout [mvp-p] hold-up time 12 ms min. current limitation auto recovery short circuit protection no auto recovery (power disconnect required) overvoltage protection by zener diode overtemperature protection auto recovery capacitive load 12 vdc models: 60000 f max. 24 vdc models: 50000 f max. 48 vdc models: 20000 f max. 54 vdc models: 10000 f max. general specifications temperature ranges C operating C25c to +70c C storage (non operating) C25c to +85c cooling internal fan (variable fan speed, temperature regulated) derating +50c to +65c: 2.2 %/k +65c to +70c: 3.3 %/k temperature coefficient 0.03 %/k humidity (non condensing) 95 % rel max. switching frequency (pulse width modulation pwm) 110 khz typ. 10% isolation voltage (60 s) C input/output 3000 vac C input/case 150 0 vac C output/case 500 vac reliability /calculated mtbf (mil-hdbk-217f, at +25c, ground benign) >100000 h all specifcations valid at nominal input voltage, full load and +25c after warm-up time unless otherwise stated. www.tracopower.com
page 3 of 5 block diagram general specifications electromagnetic compatibility (emc), emissions en 61000-3-2:2006+a1:2009+a2:2009 en 61000-3-3:2008 en 55022, class b electromagnetic compatibility (emc), immunity en 55024 C electrostatic discharge esd en 61000-4-2 2 kv / 4 kv, criteria a C rf field susceptibility en 61000-4-3 3 v/m, criteria a C electrical fast transient / burst immunity input en 61000-4-4 1 kv, criteria a C surge immunity line C neutral en 61000-4-5, 1 kv, criteria a C surge immunity line C pe, neutral C pe en 61000-4-5 2 kv, criteria a C immunity to conducted rf disturbances en 61000-4-6 3 v, criteria a C power frequency magnetic field immunity en 61000-4-8 1 a/m, criteria a C mains voltage dips and interruptions en 61000-4-11 30 % 500 ms, criteria a 95 % 10 ms, criteria a 95 % 2500 ms, criteria b emc test report www.tracopower.com/overview/txh600 degree of protection class i safety standards ul 60950-1 iec 60950-1 2nd: am 1, am 2 en 60950-1:2006/a11:2009/a1:2010/ a12:2011/a2:2013 C certification documents www.tracopower.com/overview/txh600 environment C vibration 3 axes, sine sweep, 10C500hz, 2g, 0.1 oct/min altitude during operation up to 2000 m (6560 ft) environmental compliance C reach www.tracopower.com/info/reach-declaration.pdf C r ohs rohs directive 2011/65/eu (load share) universal power supplies txh 600 series 600 watt www.tracopower.com
page 4 of 5 functions control connector c1 + sense c2 C sense c3 load share (cs) c4 gnd (internal connection to Cvout) c5 c6 remote control: open = on, short to gnd = off c7 dc-ok signal: 4-6 vdc = on, 0-1 vdc = off c8 +5 vdc aux. 10%, 0.6 a max. -v out +v out load sharing: ? difference in vout among paralleled units should be less than 1% ? output power at load share = rated power per unit x number of unit x 80% ? shorter wiring to each unit is recommended, as well as twisting +s and -s in pairs, as shown. universal power supplies txh 600 series 600 watt 8 6 4 2 7 5 3 1 8 6 4 2 7 5 3 1 8 6 4 2 7 5 3 1 8 6 4 2 7 5 3 1 -v out +v out load ps2 ps1 ps3 cs cs cs +s -s +s -s +s -s -s +s -v out +v out -v out +v out vout terminals are rated for 25 a max. at higher current connection has to be splitted. mating connector: housing: jst phdr-08vs crimp: jst sphd-002t-p0.5 connection cable with 500mm fying leads included! www.tracopower.com
outline dimensions weight: 1030 g dimensions in [mm] tolerance 0.5 mm max. mounting screw penetration: 2.0 mm page 5 of 5 sp ec i?cati ons can be changed wi thout noti ce! make sure you are using the latest documentation, downloadable at www.tracopower. com www .tracopower. com rev. july 23, 2018 connection 1 ac in iec-c13 line socket 2-4 + vout 5-7 C vout universal power supplies txh 600 series 600 watt